The following considerations, and configuration changes, must be made when connecting to the S7-1200 and S7-1500 devices
- Only global DBs can be accessed
- The optimized block access must be turned off
- The access level must be "full" and the "connection mechanism" must allow GET/PUT
- No read/write to TM/CT areas